|
EXCERPTS FROM THE ONTARIO FIRE CODE
(Ontario reg. 388/97)
|
|
Article
1.1.1.2.
Where tests, repairs or alterations are made to fire
protection installations, including sprinkler and
standpipe systems, a procedure of notification shall be
established and the procedure shall include notifying
the fire department and the building occupants where
necessary for safety in the event of a fire emergency.
|
|
Article
1.1.2.1. A
written record shall be kept of all tests and corrective
measures for a period of two years after they are made,
and the record shall be made available upon request to
the Chief Fire Official.
|
DEFINITIONS
|
|
CHECK
means
a visual observation to ensure the device or system is
in place and is not obviously damaged or obstructed.
|
|
INSPECT
means physical examination to determine that the device
or system will apparently perform in accordance with
it's intended function
|
|
TEST
means
operation of device or system to ensure that it will
perform in accordance with its intended operation or
function.
|
|
APPROVED
means approved by the Chief Fire Official
|
|
BUILDING
means any structure used or intended for supporting any use or
occupancy
|
|
CHIEF
FIRE OFFICIAL means
the Municipal Fire Chief or a member or members of the
fire department designated by the Municipal Fire Chief
or a person appointed by the Fire Marshal under
Sub-section 1.1.9.
|
|
OWNER
means
any person, firm or corporation having control over any
portion of the building or property under consideration
and includes the persons in the building or property.
|
|
RETROFIT
means the minimum performance requirements for life
safety for existing buildings.
|
|
SUPERVISORY
STAFF means
those occupants of a building who have some delegated
responsibility for the fire safety of other occupants
under the fire safety plan.
|
MANDATORY
FIRE SAFETY MAINTENANCE SCHEDULE
|
Whenever a defect or deficiency is
discovered in fire safety equipment, CORRECTIVE
ACTION must be taken IMMEDIATELY by the owner
or his authorized agent.
|
DAILY
|
Fire
Code Reference #
|
|
(1)
CHECK exit signs to ensure they are in
clean and legible condition.
|
2.7.3.1.
|
|
(2)
CHECK exit lights to ensure they are
illuminated and in good repair.
|
2.7.3.2.
|
|
(3)
CHECK torches, regulators and welding
equipment for defects.
|
5.17.2.6.
|
|
(4) CHECK
fire alarm system AC power lamp.
|
6.3.2.1.
|
|
(5)
CHECK central alarm and control
facility to ensure that no “trouble” is indicated.
|
6.3.2.2.
|
|
(6)
CHECK tank heating equipment and accessories to ensure they are in operating
condition and heater valves are open
|
6.6.2.2.
|
|
(7) CHECK temperature of water contained in
tanks to ensure it does not fall below the freezing
temperature
|
6.6.2.3
|
|
(8)
CHECK temperature of tank enclosure for tanks in
buildings to ensure temperature of tank does not fall
below the freezing temperature
|
6.6.2.4.
|
|
(9)
CHECK temperature of fire pump rooms
during freezing weather.
|
6.6.3.2.
|
|
WEEKLY
|
|
(1)
CHECK hoods, filters and ducts in ventilation
systems subject to accumulation of combustible deposits.
|
2.6.1.4.
|
|
(2)
CHECK that sprinkler system control
valves are open.
|
6.5.3.1.
|
|
(3)
CHECK that dry pipe sprinkler system
air pressure is being maintained.
|
6.5.3.3.
|
|
(4)
INSPECT valves controlling fire
protection water supplies.
|
6.6.1.2.
|
|
(5)
CHECK the water level and air pressure
for fire protection system water tanks.
|
6.6.2.12.
|
|
(6)
INSPECT relief valves on air and water
supply lines of fire protection system pressure tanks.
|
6.6.2.13.
|
|
(7)
CHECK water level in fire pump reservoirs.
|
6.6.3.1.
|
|
(8) INSPECT
and
operate all fire pumps
|
6.6.3.3.
|
|
(9) CHECK
all
components of emergency generator system set under at
least 50% of the rated load for 30 minutes.
|
6.7.1.1.
|
|
MONTHLY
|
|
(1)
INSPECT all doors in fire separations.
|
2.2.3.4.
|
|
(2)
INSPECT and TEST emergency
lighting systems, batteries, units and lamps.
|
2.7.3.3.
|
|
(3)
CONDUCT fire drills for Supervisory
staff in day care and health care facilities.
|
2.8.3.2.
|
|
(4)
TEST all welding equipment.
|
5.17.2.6.
|
|
(5)
INSPECT all portable fire extinguishers.
|
6.2.7.2.
|
|
(6)
TEST fire alarm system and check all
components including standby power batteries.
|
6.3.2.1.
|
|
(7)
TEST the voice communication system.
|
6.3.2.3.
|
|
(8)
INSPECT all fire hose cabinets.
|
6.4.2.1.
|
|
(9)
TEST the sprinkler system alarm.
|
6.5.5.2.
|
|
(10)
INSPECT the water level in gravity fire
protection water tanks.
|
6.6.2.8.
|
|
EVERY TWO MONTHS
|
|
(1)
TEST sprinkler system central station
connections.
|
6.5.5.7.
|
|
EVERY THREE MONTHS
|
|
(1)
CONDUCT a fire alarm drill for
supervisory staff in all high-rise buildings.
|
2.8.3.2.
|
|
(2)
TEST all fire safety devices in high
buildings as defined by sub-section 3.2.6. of the
Building Code.
|
7.2.1.1.
|
|
(3)
TEST firefighters elevator for proper
operation.
|
7.2.1.2.
|
|
EVERY SIX MONTHS
|
|
(1)
INSPECT fire protection equipment for
commercial cooking equipment.
|
2.6.1.13.
|
|
(2)
CONDUCT total evacuation fire alarm
drills in schools attended by children. (Conduct 3 times
in both spring and fall terms.)
|
2.8.3.2.
|
|
(3)
TEST gate valve supervisory switch and
other sprinkler and fire protection system supervisory
devices.
|
6.5.5.7.
|
|
(4)
CHECK and clean crankcase, breathers,
governors and linkages on emergency generator sets.
|
6.7.1.1.
|
|
(5)
INSPECT and maintain special
extinguishing systems.
|
6.8.1.1.
|
|
(6)
INSPECT elevators in an elevator shaft
that is intended for use as a smoke shaft and ensure
that they function as designed under an alarm condition.
|
6.7.3.1.
|
|
ANNUALY
|
|
(1)
INSPECT fire dampers and fire stop
flaps.
|
2.2.3.7.
|
|
(2)
INSPECT all chimneys, flues and flue pipes.
|
2.6.1.5.
|
|
(3)
INSPECT disconnect switches for mechanical air
conditioning and ventilation systems.
|
2.6.1.8.
|
|
(4)
CLEAN chimney spark arrestors.
|
2.6.3.3.
|
|
(5)
CONDUCT fire alarm drills for
supervisory staff in buildings with fire alarm systems.
|
2.8.3.2.
|
|
(6)
CONDUCT maintenance procedures for fire
extinguishers.
|
6.2.7.1.
|
|
(7)
CONDUCT a test of the fire alarm system
by persons with qualifications acceptable to the Chief
Fire Official.
|
6.3.2.1.
|
|
(8)
CONDUCT a test of the voice
communication system by persons with qualifications
acceptable to the Chief Fire Official.
|
6.3.2.3.
|
|
(9)
INSPECT all standpipe hose valves to ensure
they are tight and no water is leaking into the hose.
|
6.4.2.4.
|
|
(10)
INSPECT and re-rack all standpipe hose.
|
6.4.2.5.
|
|
(11)
INSPECT exposed sprinkler pipe hangers to
ensure they are in good repair.
|
6.5.3.2.
|
|
(12)
CHECK all sprinkler heads to ensure
they are free from damage, corrosion, grease, dust,
paint or whitewash.
|
6.5.3.5.
|
|
(13)
INSPECT dry pipe valve water priming
level.
|
6.5.4.3.
|
|
(14)
INSPECT fire department connections for caps,
wear, rust or obstructions.
|
6.5.4.4.
|
|
(15)
CONDUCT sprinkler system alarm testing
using the most hydraulically remote connection.
|
6.5.5.3.
|
|
(16)
CONDUCT a dry pipe system trip test.
|
6.5.5.4.
|
|
(17)
CONDUCT a main drain flow test of the
sprinkler water supply.
|
6.5.5.5.
|
|
(18)
INSPECT fire protection water supply tanks.
|
6.6.2.1.
|
|
(19)
INSPECT the cathodic protection of steel water
tanks.
|
6.6.2.7.
|
|
(20)
INSPECT all parts of a gravity fire protection
water tanks.
|
6.6.2.9.
|
|
(21)
CONDUCT a fire pump flow test.
|
6.6.3.5.
|
|
(22)
INSPECT all hydrants, and after each use.
|
6.6.5.1.
|
|
(22)
INSPECT all hydrants shall be flow tested.
|
6.6.5.7.
|
|
(24)
CONDUCT general engine and generator maintenance
and engine tune-ups for emergency generator sets.
|
6.7.1.1.
|
|
(25)
INSPECT closure at the top of smoke shaft.
|
7.2.3.1.
|
|
(26)
INSPECT controls for air-handling used for
venting.
|
7.2.3.1.
|
|
EVERY
TWO YEARS
|
|
(1)
CHECK steel fire protection tanks for corrosion.
|
6.6.2.5.
|
|
(2)
INSPECT all fire protection water tanks,
connected to a non-potable water supply for sediment.
|
6.6.2.6.
|
|
(3)
CHECK valve adjustments and torque heads for
emergency generator engines.
|
6.7.1.1.
|
|
EVERY
THREE YEARS
|
|
(1)
CLEAN and service injector nozzles and check
valve adjustments for emergency generator diesel
engines.
|
6.7.1.1.
|
|
EVERY
FIVE YEARS
|
|
(1)
Hydrostatically TEST carbon dioxide and water
type extinguishers.
|
6.2.7.1.
|
|
(2)
Hydrostatically TEST dry standpipe system.
|
6.4.3.6.
|
|
(3)
INSPECT fire protection water tank, connected to
a potable water supply, for accumulation of sediment.
|
6.6.2.6.
|
|
(4)
CHECK insulation of generator windings.
|
6.7.1.1.
|
|
(5)
INSPECT closures in vent openings into smoke
shafts.
|
7.2.3.1.
|
|
EVERY
SIX YEARS
|
|
(1)
REPLACE the extinguishing agent in dry chemical
fire extinguishers.
|
6.2.7.1.
|
|
EVERY
TWELVE YEARS
|
|
(1)
Hydrostatically TEST dry chemical and vaporizing
liquid fire extinguishers.
|
6.2.7.1.
|
|
EVERY
FIFTEEN YEARS
|
|
(1)
INSPECT dry pipe sprinkler systems for pipe
obstructions - flush the system.
|
6.5.4.2.
|
|
AS
REQUIRED
|
|
(1)
CHECK doors in fire separations to ensure they
are closed.
|
2.2.3.5.
|
|
(2)
CHECK lint traps in laundry equipment.
|
2.4.1.5.
|
|
(3)
ENSURE streets, yards and private roadways that
are provided for fire department access are kept clear.
|
2.5.1.3.
|
|
(4)
CHECK corridors and ensure they are maintained
free of obstructions.
|
2.7.1.7.
|
|
(5)
CLEAN any combustible dust-producing operations.
|
5.10.1.2.
|
|
(6)
CLEAN residue in spray booths.
|
5.12.7.2.
|
|
(7)
VACUUM, clean and dust any dry-powder finishing
operations.
|
5.14.6.8.
|
|
(8)
INSPECT clean and maintain all industrial ovens
and associated ductwork.
|
5.18.5.1.
|
|
(9)
INSPECT sprinkler system auxiliary drains.
|
6.5.4.1.
|
|
(10)
MAINTAIN smoke control equipment in a manner to
ensure satisfactory operation.
|
7.3.1.1.
|
|
(11)
INSPECT and TEST all equipment used in
conjunction with smoke control measures.
|
7.3.1.2.
|
|
(12)
INSPECT and TEST all equipment used in
conjunction with smoke control systems.
|
7.3.1.3.
|